Srikakulapu, R.Vinatha Urundady, U.2026-02-062017Asia-Pacific Power and Energy Engineering Conference, APPEEC, 2017, Vol.2017-November, , p. 1-521574839https://doi.org/10.1109/APPEEC.2017.8309000https://idr.nitk.ac.in/handle/123456789/31830Permanent magnet synchronous generator (PMSG) based offshore wind farm is connected to the onshore grid by voltage source converter (VSC) - HVDC link. The wind farm side VSC controls the AC voltage, and grid side VSC controls the reactive power and DC link voltage. This paper presents a non-linear control method for improving the robustness of the controller for VSC-HVDC link. A hybrid controller is designed using sliding mode control (SMC) and proportional-integral (PI) control. Mathematical modeling of the hybrid controller is presented. This hybrid controller has the capability of Fault Ride-Through and transient stability of VSC-HVDC link. This hybrid controller is simulated using the MATLAB/Simulink software and it is observed that the controller provides better performance. Transient stability is ensured by creating a symmetrical fault at the grid side in the simulation. © 2017 IEEE.AC voltage controlDC voltage controlHigh voltage direct-currentOffshore wind farmReactive power controlSliding mode controlVoltage source converterA hybrid controller design for VSC-HVDC transmission system for PMSG based offshore wind farm