Abraham, N.M.Parameswaran, A.P.Abraham, R.J.2026-02-0620112011 International Conference on Power and Energy Systems, ICPS 2011, 2011, Vol., , p. -https://doi.org/10.1109/ICPES.2011.6156663https://idr.nitk.ac.in/handle/123456789/33002This paper deals with automatic generation control of an interconnected thermal non-reheat power system in continuous mode by employing a Thyristor Controlled Series Capacitor (TCSC) in series with the line. Damping of the system frequency and tie-line power oscillations by controlling the reactance of the TCSC is presented. Gain values of the integral controllers are optimised using the integral squared error method by providing a step load disturbance in each of the areas by minimising a quadratic performance index. It is reported that TCSC can dampen the tie-line and power oscillations commendably under sudden load disturbances in any of the areas. © 2011 IEEE.Area Control ErrorAutomatic Generation Control (AGC)Integral Squared Error (ISE) techniqueInter Area Tie-line PowerTCSC ControllerEffects of Thyristor Controlled Series Capacitor (TCSC) on oscillations in tie-line power and area frequencies in an interconnected non-reheat thermal power system