Punekar, G.S.Antony, D.Bhavanishanker, T.Nagamani, H.N.Kishore, N.K.2020-03-302020-03-3020132013 IEEE 1st International Conference on Condition Assessment Techniques in Electrical Systems, IEEE CATCON 2013 - Proceedings, 2013, Vol., , pp.386-390https://idr.nitk.ac.in/handle/123456789/8140Using the experimental data obtained from an Acoustic Emission Partial Discharge (AEPD) system, efforts are made to locate the source of Partial discharge (PD) with a transformer tank. The AEPD data with 8 sensors (available in the literature) is numerically experimented with a Genetic Algorithm, although minimum of 4 sensors only are necessary for identifying the location. With eight sensors, four sensors considered at a time, form 70 ( 8C4) combination of sensors. The effect, implication and usage of superfluous sensor data in identifying the location with GA is analyzed and reported. Results are compared with Newton's method. � 2013 IEEE.Genetic algorithm in location identification of AEPD source: Some aspectsBook chapter