Saralaya, S.Manjunatha Sharma, K.M.2026-02-052018International Journal of Power Electronics, 2018, 9, 2, pp. 214-2281756638Xhttps://doi.org/10.1504/IJPELEC.2018.090717https://idr.nitk.ac.in/handle/123456789/25301An improved control strategy based on power balancing algorithm without using current sensors is presented in this paper. The mathematical model of this improved method is discussed. Point of common coupling (PCC) voltage and DC link voltage are taken as voltage commands for reference signal generation. Sinusoidal pulse width modulation is used to generate the pulses for distribution static compensator (DSTATCOM). Proportional integral (PI) controller is used to control the PCC voltage and DC link voltage of the voltage source converter of DSTATCOM. This improved method is tested for different load conditions using PSCAD/EMTDC package. The improved control strategy is validated by simulation results for linear and non-linear load conditions. © © 2018 Inderscience Enterprises Ltd.Electric fault currentsPower convertersPower qualityQuality controlStatic synchronous compensatorsTwo term control systemsVoltage controlControl strategiesCoupling voltageCurrent sensorsDistribution static compensatorImproved controlsPoint of common couplingProportional integral controllersTotal harmonic distortionsVoltage sourceVoltage source converterControllersAn improved control strategy without current sensors for DSTATCOM