Please use this identifier to cite or link to this item: https://idr.nitk.ac.in/jspui/handle/123456789/12253
Full metadata record
DC FieldValueLanguage
dc.contributor.authorAntony, D.
dc.contributor.authorPunekar, G.S.
dc.date.accessioned2020-03-31T08:38:52Z-
dc.date.available2020-03-31T08:38:52Z-
dc.date.issued2018
dc.identifier.citationIEEE Transactions on Power Delivery, 2018, Vol.33, 4, pp.1679-1688en_US
dc.identifier.urihttp://idr.nitk.ac.in/jspui/handle/123456789/12253-
dc.description.abstractThe combined acoustic-electrical system is used in the factory or plant environment for the partial discharge (PD) source localization in power transformers. A noniterative method for this combined acoustic-electrical PD-locator-system is devised and presented in this paper for the first time. It employs three acoustic emission (AE) sensors. The proposed method is compared with the existing noniterative method used in the all-acoustic system, which employs four AE sensors. The comparative study shows that the proposed method can locate the PD source irrespective of its position within the tank, whereas the prevailing noniterative method for the all-acoustic system fails to locate the PD source at certain positions within the tank. The effect of the sensor positioning on the performance of the method is studied, and some guidelines for the sensor placement on the transformers tank wall in a factory or plant environment are suggested. The proposed method is also applied to the data taken from the published literature. The localization results are compared with those of an existing iterative method (Newton's method) to prove its superiority in terms of computational time. 1986-2012 IEEE.en_US
dc.titleNoniterative Method for Combined Acoustic-Electrical Partial Discharge Source Localizationen_US
dc.typeArticleen_US
Appears in Collections:1. Journal Articles

Files in This Item:
There are no files associated with this item.


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.