Abstract
This paper examines the impact of power grid strength, power level, rotor side converter (RSC) controller parameters, and shaft parameters on the small-signal stability of a doubly fed induction generator (DFIG)-integrated power system. In each of the parametric variations, both sub-and super-synchronous operating conditions of DFIG are considered. Using the eigenvalue technique the effects of parameter are analyzed and these eigen-inferences are further validated using time-domain simulations. From the analysis it is observed that the in sub-synchronous operating point, weak-grid conditions and RSC controller parameters may result in small-signal instability. © 2022 IEEE.
Description
Keywords
Doubly fed induction generator (DFIG), Eigenvalue analysis, Small-signal stability, Time-domain simulation
Citation
2022 IEEE International Power and Renewable Energy Conference, IPRECON 2022, 2022, Vol., , p. -