High-efficiency improved 12kW switched mode telecom rectifier

dc.contributor.authorPrakash, P.S.
dc.contributor.authorKalpana, R.
dc.contributor.authorSingh, B.
dc.contributor.authorBhuvaneswari, G.
dc.date.accessioned2020-03-30T10:18:12Z
dc.date.available2020-03-30T10:18:12Z
dc.date.issued2016
dc.description.abstractIn this paper an improved switched mode telecom rectifier for a 12kW telecommunication system is presented. An improved telecom rectifier is a combination of phase-shift transformer based ac-dc converter and passive high pass filter. The phase-shift transformer and high pass filter is realized with a fractional magnetic rating of the load. The supply current is almost sinusoidal with low total harmonic distortion, and the power factor (PF) is close to unity. The complete design of phase-shift transformer based ac-dc converter and passive high pass filter is presented in this paper. The 12kW telecom rectifier is designed, modeled and simulated to reduce the total harmonic distortion (THD) of the input ac mains current and to improve the power factor. A laboratory prototype of phase-shift transformer based ac-dc converter is developed and the results are presented to validate the design topology. � 2015 IEEE.en_US
dc.identifier.citation2015 IEEE International WIE Conference on Electrical and Computer Engineering, WIECON-ECE 2015, 2016, Vol., , pp.382-386en_US
dc.identifier.urihttps://idr.nitk.ac.in/handle/123456789/8199
dc.titleHigh-efficiency improved 12kW switched mode telecom rectifieren_US
dc.typeBook chapteren_US