Optimal Sizing, Placement and Performance Analysis of DSTATCOM with Improved Controller without Current Sensors

dc.contributor.authorSaralaya, S.
dc.contributor.authorManjunatha Sharma, K.
dc.date.accessioned2026-02-06T06:35:57Z
dc.date.issued2021
dc.description.abstractThe performance analysis of Distribution Static Compensator (DSTATCOM), when it is placed in an optimized location with an improved controller without current sensors is presented in this paper. To obtain optimal location, Ant colony optimization technique is used for the placement of DSTATCOM. To incorporate this compensator in load flow analysis, the modelling is done and rating of DSTATCOM is obtained. The performance analysis of improved controller is presented after placing the DSTACOM in optimized location with optimized size. The actual voltage at bus where DSTATCOM is placed and DC voltage of the converter is taken as control parameters. The proposed optimization placement technique is tested for 207 bus practical distribution system using MATLAB. The performance analysis of studied systems with controller for different operating scenarios such as sag, swell are investigated in MATLAB/SIMULINK software environment. © 2021 IEEE.
dc.identifier.citation4th International Symposium on Devices, Circuits and Systems, ISDCS 2021 - Conference Proceedings, 2021, Vol., , p. -
dc.identifier.urihttps://doi.org/10.1109/ISDCS52006.2021.9397892
dc.identifier.urihttps://idr.nitk.ac.in/handle/123456789/30165
dc.publisherInstitute of Electrical and Electronics Engineers Inc.
dc.subjectAnt Colony algorithm
dc.subjectDistribution Static Compensator
dc.subjectLoss Reduction
dc.subjectRadial distribution system
dc.subjectVoltage sag
dc.subjectVoltage source converter
dc.subjectVoltage Swell
dc.titleOptimal Sizing, Placement and Performance Analysis of DSTATCOM with Improved Controller without Current Sensors