Inrush Current Parameters Associated with Back-to-Back Switching of Capacitors in a Bank

dc.contributor.authorRamesh, M.
dc.contributor.authorNagamani, H.N.
dc.contributor.authorVaidhyanathan, V.
dc.contributor.authorPunekar, G.S.
dc.date.accessioned2026-02-05T09:32:32Z
dc.date.issued2017
dc.description.abstractBack-to-back switching of 50 kVAr capacitors, in a capacitor bank of 200 kVAr is investigated experimentally. The switching inrush currents in a three-phase, 200 kVAr, 415 V Automatic Power Factor Correction panel at power frequency are captured in the laboratory. The characterizing features of inrush current are reported and analyzed. The commercially available two makes of switches (contactors) are used to compare the inrush currents with and without their pre-insertion resistors (PIR). The inrush current scenario of the experimental setup is modeled in EMTDC/PSCAD to ascertain the results. The ratio I<inf>peak</inf>/I<inf>N</inf> for both the contactors without PIR exceeded the limit mentioned in IEC 60831-1 Ed 3.0 : 2014. © 2017, Copyright © Taylor & Francis Group, LLC.
dc.identifier.citationElectric Power Components and Systems, 2017, 45, 3, pp. 279-287
dc.identifier.issn15325008
dc.identifier.urihttps://doi.org/10.1080/15325008.2016.1201705
dc.identifier.urihttps://idr.nitk.ac.in/handle/123456789/25688
dc.publisherTaylor and Francis Inc. 325 Chestnut St, Suite 800 Philadelphia PA 19106
dc.subjectElectrical engineering
dc.subjectMechanical engineering
dc.subjectReactive power
dc.subjectTransients
dc.subjectAPFC panel
dc.subjectCapacitor bank
dc.subjectcontactor
dc.subjectIn-rush current
dc.subjectParallel switching
dc.subjectPower factors
dc.subjectSwitching
dc.titleInrush Current Parameters Associated with Back-to-Back Switching of Capacitors in a Bank