DSC filter based unit vector estimator for reference generation and control of dynamic voltage restorer

No Thumbnail Available

Date

2017

Authors

Kasyap, M.S.
Karthikeyan, A.
Perumal, B.V.
Nagamani, C.

Journal Title

Journal ISSN

Volume Title

Publisher

Abstract

DVR control requires a robust algorithm for computing grid voltage magnitude and phase angle. Conventional SRF-PLL performs poorly as it cannot filter out negative sequence voltages and harmonics that could occur in the grid voltage. In this paper a Positive and Negative Sequence Extractor (PNSE) is formed by a Delayed Signal Cancellation (DSC) filter, which filters harmonics and extracts Instantaneous Symmetrical Components (ISC) of the source voltage in stationary reference frame. The phase angle information of the grid voltage is derived by computing the unit vectors of the ISC in stationary frame. This eliminates the need for a conventional PLL and thus simplifies the reference generation algorithm. A PI controller tracks the capacitor reference voltage in synchronous reference frame to restore the fundamental load voltage while resonant controllers are tuned to mitigate the lower order odd harmonics in the load voltage. Simulation studies carried out in PSCAD/EMTDC for a Medium Voltage DVR model shows that the presented control works effectively for all the test cases considered such as voltage sags and harmonics. � 2016 IEEE.

Description

Keywords

Citation

2016 IEEE 7th Power India International Conference, PIICON 2016, 2017, Vol., , pp.-

Endorsement

Review

Supplemented By

Referenced By