Transient Analysis of LCC based HVDC Offshore Wind Farms using DIgSILENT PowerFactory
No Thumbnail Available
Date
2021
Authors
Journal Title
Journal ISSN
Volume Title
Publisher
Institute of Electrical and Electronics Engineers Inc.
Abstract
Offshore wind farms (OWFs) connect to onshore grids through HVDC cable. Severe grid faults mainly affect the offshore wind farms and HVDC cables. As a result, the transient response of the system deteriorates. Therefore, this paper aims for the transient analysis of line commutated current converter (LCC) based HVDC system under 3-phase fault. The paper proposes the DIgSILENT Simulation Language (DSL) oriented PI control for the both rectifier and inverter stations. The whole HVDC system is modelled in DIgSILENT PowerFactory software for the better transient response. In addition, the PI control and voltage dependent current order limiter (VDCOL) are designed in this PowerFactory software. The advantage of this software is that it improves the transient behaviour and stability of the system. These controllers limit the inrush current and voltage fluctuations at the moment of fault occurrence and clearance. The simulation results under fault indicate the better transient response with the system stability. © 2021 IEEE.
Description
Keywords
DIgSILENT, HVDC, LCC, OWFs
Citation
7th Iran Wind Energy Conference, IWEC 2021, 2021, Vol., , p. -