Effects of Thyristor Controlled Series Capacitor (TCSC) on oscillations in tie-line power and area frequencies in an interconnected non-reheat thermal power system

dc.contributor.authorAbraham, N.M.
dc.contributor.authorParameswaran, A.P.
dc.contributor.authorAbraham, R.J.
dc.date.accessioned2026-02-06T06:40:32Z
dc.date.issued2011
dc.description.abstractThis paper deals with automatic generation control of an interconnected thermal non-reheat power system in continuous mode by employing a Thyristor Controlled Series Capacitor (TCSC) in series with the line. Damping of the system frequency and tie-line power oscillations by controlling the reactance of the TCSC is presented. Gain values of the integral controllers are optimised using the integral squared error method by providing a step load disturbance in each of the areas by minimising a quadratic performance index. It is reported that TCSC can dampen the tie-line and power oscillations commendably under sudden load disturbances in any of the areas. © 2011 IEEE.
dc.identifier.citation2011 International Conference on Power and Energy Systems, ICPS 2011, 2011, Vol., , p. -
dc.identifier.urihttps://doi.org/10.1109/ICPES.2011.6156663
dc.identifier.urihttps://idr.nitk.ac.in/handle/123456789/33002
dc.subjectArea Control Error
dc.subjectAutomatic Generation Control (AGC)
dc.subjectIntegral Squared Error (ISE) technique
dc.subjectInter Area Tie-line Power
dc.subjectTCSC Controller
dc.titleEffects of Thyristor Controlled Series Capacitor (TCSC) on oscillations in tie-line power and area frequencies in an interconnected non-reheat thermal power system