Electric Fields due to A 500 kV Quadruple Circuit Transmission Line: Some Aspects Concerning Public Exposure

No Thumbnail Available

Date

2019

Authors

Prasad K.Y.
Punekar G.S.

Journal Title

Journal ISSN

Volume Title

Publisher

Abstract

Extra high voltage and Ultra high voltage transmission lines produce high intensity electric fields (E-fields). These high intensity E-fields, which are in the vicinity of such lines, would result into adverse effects on humans. E-fields at the ground level should be below a certain limit as specified by the International Commission on Non-Ionizing Radiation Protection (ICNIRP) guidelines from the point of view of public exposure. In the present study the E-fields due to the Quadruple circuit transmission line is estimated and analyzed. Finite element method is used to calculate the E-fields by placing the conductors at the permitted worst-case sag (8%) position for the chosen span. These results are compared with those available in the literature with 4 % sag. © 2019 IEEE.

Description

Keywords

Citation

4th International Conference on Electrical, Electronics, Communication, Computer Technologies and Optimization Techniques, ICEECCOT 2019 , Vol. , , p. 332 - 335