Large-Signal Performance of Synchronous Machine Models in Power Systems

dc.contributor.authorKotian, S.M.
dc.contributor.authorShubhanga, K.N.
dc.date.accessioned2026-02-06T06:38:45Z
dc.date.issued2017
dc.description.abstractIn this paper, the IEEE-specified generator models such as the equivalent circuit (EC) models and the operational inductance (OI) models are compared to analyze the influence of the differences in the standard transfer functions among these models on the large-disturbance rotor-angle stability (or transient stability) of the power system. The large disturbances such as unsymmetrical and symmetrical short-circuit faults are considered. Critical clearing time (CCT) corresponding to first swing stability is evaluated for each of the models and compared. Such a study is of major importance when comparing results obtained using different commercial grade packages. © 2016 IEEE.
dc.identifier.citationIEEE International Conference on Power Electronics, Drives and Energy Systems, PEDES 2016, 2017, Vol.2016-January, , p. 1-6
dc.identifier.urihttps://doi.org/10.1109/PEDES.2016.7914507
dc.identifier.urihttps://idr.nitk.ac.in/handle/123456789/31859
dc.publisherInstitute of Electrical and Electronics Engineers Inc.
dc.subjectCritical clearing time
dc.subjectSynchronous machine models
dc.subjectTransient stability
dc.titleLarge-Signal Performance of Synchronous Machine Models in Power Systems

Files