Investigations on Single-Phasing Effect of Zigzag Autoconfigured Transformer Based 12-Pulse Rectifier

No Thumbnail Available

Date

2018

Authors

Kalpana, R.
Saravana, Prakash, P.
Vidyasagar, V.S.
Singh, B.

Journal Title

Journal ISSN

Volume Title

Publisher

Abstract

High power industrial loads are often fed from front-end multi-pulse rectifier as its ability to effectively and inexpensively mitigate the harmonics on the AC side is achieved by the multi-pulse autoconfigured transformer. This paper analyzes and investigates the operability of the zigzag autoconfigured transformer based 12-pulse rectifier when one of the input terminals is open, i.e., single-phasing. Contrary to the prior art multi-pulse rectifiers, the availability of neutral point in zigzag autoconfigured transformer results in normal operation at DC side during single-phasing. A detailed MATLAB Simulation is carried out to understand the single-phasing operation of the zigzag autoconfigured transformer. Further, the experimental results from the laboratory prototype are presented to validate the simulated results. � 2018 IEEE.

Description

Keywords

Citation

Proceedings of 2018 IEEE International Conference on Power Electronics, Drives and Energy Systems, PEDES 2018, 2018, Vol., , pp.-

Endorsement

Review

Supplemented By

Referenced By