Thermal effects on acoustic emission based PD in transformer oil: A study

dc.contributor.authorBhavani Shanker, T.
dc.contributor.authorNagamani, H.N.
dc.contributor.authorPunekar, G.S.
dc.date.accessioned2026-02-06T06:40:22Z
dc.date.issued2012
dc.description.abstractTransformers operate at different service conditions in the field resulting in operating temperatures of oil and winding, much above ambient temperature. Acoustic emissions due to partial discharge activity in transformer insulation system, including transformer oil, have been investigated by a few researchers at temperatures ranging from 25°C to 40°C. It is more realistic to consider the study at service temperature which could be around 50°C to 70°C; depending on the service conditions and type of insulation employed. The paper deals with acoustic partial discharge behaviour in transformer oil at temperatures ranging from 30°C to 75°C along with some of the properties of transformer oil. © 2012 IEEE.
dc.identifier.citationProceedings of the IEEE International Conference on Properties and Applications of Dielectric Materials, 2012, Vol., , p. -
dc.identifier.urihttps://doi.org/10.1109/ICPADM.2012.6318903
dc.identifier.urihttps://idr.nitk.ac.in/handle/123456789/32890
dc.subjectacoustic emission
dc.subjectacoustic energy
dc.subjectfrequency content
dc.subjectPartial Discharge (PD)
dc.subjectspecific resistivity
dc.subjecttan δ
dc.subjecttotal gas content (TGC)
dc.titleThermal effects on acoustic emission based PD in transformer oil: A study