Faculty Publications

Permanent URI for this communityhttps://idr.nitk.ac.in/handle/123456789/18736

Publications by NITK Faculty

Browse

Search Results

Now showing 1 - 5 of 5
  • Item
    Theoretical Evaluation of Energy Performance of a Vapour Compression Refrigeration System Using Sustainable Refrigerants
    (Springer, 2020) Vali, S.V.; Ashok Babu, T.P.
    The chief goal of this present investigation is to evaluate performance parameters of various sustainable refrigerants as R22 alternatives. In this investigation apart from R290, R134a and R22, twelve mixture refrigerants were developed at various composition. Results showed that energy efficiency ratio (EER) of mixture refrigerant MR40 (R290/R134a 95/5 in mass%) (4.546) stood greatest among twelve investigated alternatives and it was closer to the EER of R22 (4.602). Compressor discharge temperature of MR40 was lower than R22 by 16.020C. Volumetric refrigeration capacity of MR40 (3424 kJ/m3) was relatively lesser than R22 (3801 kJ/m3). Power spent per ton of refrigeration (PPTR) of MR40 (0.773 kW/TR) stood lowest among twelve investigated alternatives and it was fairly greater than R22 (0.764 kW/TR). Global warming potential (GWP100) of MR40 (68) was very low compared to R22 (1760). Overall, performance of MR40 was closer to R22, when compared with all the twelve investigated alternatives, and hence, it might be treated as a suitable replacement to refrigerant R22. © 2020, Springer Nature Singapore Pte Ltd.
  • Item
    Analytical computation of thermodynamic performance of various new eco-friendly alternative refrigerants applicable for air conditioners
    (Springer Science and Business Media Deutschland GmbH info@springer-sbm.com, 2021) Vali, S.V.; Ashok Babu, T.P.; Mahapatra, D.; Saboor, S.; Gorantla, K.K.; Sai Siva Subramanyam, V.
    The objective of the present investigation is to do the theoretical thermodynamic analysis of various new eco-friendly R22 substitutes used in vapour compression refrigeration (VCR) cycle. In this work, nine mixture refrigerants were considered at different compositions. Thermodynamic properties of all the considered refrigerants were developed and the same properties were used in the performance analysis of alternative refrigerants. Standard VCR cycle was considered for the thermodynamic assessment of alternative refrigerants. The working conditions considered are expressed as Te = 7.2 °C, Tk = 54.4 °C, ΔTsup = 11.1 °C and ΔTsub = 8.3 °C, respectively. Results revealed that the COP of mixture refrigerant MR20 (R600a/R134a/R1270 5/47.5/47.5 in mass%) was 2.02% higher than the COP of R22 and other nine investigated refrigerants. Discharge temperature of compressor obtained for MR20 was 11.79 °C lower compared to that of R22. Compressor power obtained for MR20 was 1.96% lower than that of R22. Volumetric refrigeration capacity obtained for MR20 was relatively closer to that of R22. GWP100 of MR20 (619) was lower compared to the GWP100 of R22 (1760). Overall, the performance of mixture refrigerant MR20 was better compared to all the considered R22 alternatives, and therefore it might be an appropriate candidate to replace R22 used in air conditioners. © Springer Nature Singapore Pte Ltd 2021.
  • Item
    Thermodynamic performance analysis and flammability study of various new ozone friendly non azeotropic refrigerant mixtures as alternatives to replace R22 used in residential air conditioners
    (International Information and Engineering Technology Association info@iieta.org, 2018) Vali, S.V.; Ashok Babu, T.P.A.
    The present study investigates the theoretical thermodynamic performance analysis and flammability study of various new ozone friendly refrigerants as replacements to R22. In this work, five non azeotropic refrigerant blends comprising of R152a, R134a, R32, R290 and R1270, at various compositions were developed. Flammability study of all the five refrigerant mixtures considered were carried out by using Refrigerant Flammability (RF) number. The cycle followed during the performance investigation of refrigerants was the actual vapour compression refrigeration cycle. Thermodynamic performance characteristics of all the five investigated refrigerants were compared with the baseline refrigerant R22. Theoretical results showed that COP of refrigerant M40 was 0.51% higher, compared to R22 and the five refrigerants studied. Compressor discharge temperature of M40 was lowered by 11.6°C compared to R22. Power consumed to produce per ton of refrigeration of M40 was 0.52% lower, compared to R22 and the five refrigerants considered. Heat transfer rate through the condenser for M40 was 3.66% higher than R22. Volumetric refrigeration capacity of M40 was the highest among the five studied refrigerants and it was very close to the volumetric capacity of R22. Flammability analysis revealed that all the five investigated refrigerant mixtures were classified into the weakly flammable category. Overall, the thermodynamic performance of new ternary blend M40 (R32/R134a/R1270 5/60/35 by mass percentage) was higher than R22 with reasonable saving in power consumption and hence, M40 is a viable candidate to replace R22. © 2018 International Information and Engineering Technology Association. All Rights Reserved.
  • Item
    Thermodynamic analysis of window air conditioner using sustainable refrigerant R290/RE170 and R1270/RE170 blends as substitutes to refrigerant R22
    (International Information and Engineering Technology Association info@iieta.org, 2019) Vali, S.V.; Setty, A.B.T.P.
    The present work emphasis on theoretical computation of thermodynamic performance of window air conditioner using various sustainable R290/RE170 and R1270/RE170 refrigerant mixtures as substitutes to R22. In this work, apart from R407C, twelve new binary mixtures comprising of R290, R1270 and RE170 at various compositions were developed. And also in this investigation, a MATLAB code was developed to compute the thermodynamic performance characteristics of various considered R22 alternatives at Tk=54.4 0C and Te=7.2 °C. The various performance characteristics computed are mass flow rate, refrigeration effect, compressor work, coefficient of performance (COP), pressure ratio, compressor discharge temperature, power consumed per ton of refrigeration, condenser heat rejection and volumetric cooling capacity. Results showed that the COP of refrigerant mixture RM7 (R1270/RE170 95/5 by mass %) was the highest among twelve refrigerants studied and it was 0.23 % higher than R22. Pressure ratio of RM7 (3.174) was 7.49 % lower than that of R22 (3.431). Compressor discharge temperature of all the twelve investigated refrigerants was lower in the range of 9.35 0C to 17.15 0C when compared with R22. Power consumed per ton of refrigeration of RM7 was 0.27 % lower than that of R22. Volumetric cooling capacity of RM7 (3833 kJ/m3) was very close to that of R22 volumetric capacity (3863 kJ/m3). Heat transfer through condenser of RM7 (6.372 kW) was similar to that of R22 (6.377 kW). Overall, thermodynamic performance of RM7 matches well with the performance of base line refrigerant R22 and hence, refrigerant RM7 can be considered as sustainable alternative to R22 used in air conditioners. © 2019 International Information and Engineering Technology Association. All rights reserved.
  • Item
    Theoretical energy performance assessment and environmental impact of various new ozone-friendly refrigerants used in residential air conditioners
    (SAGE Publications Ltd, 2020) Vali, S.V.; Ashok Babu, T.P.
    This study focuses on energy performance investigation and environmental impact analysis of various new ecofriendly refrigerant blends as alternatives to high global warming potential refrigerant R22 theoretically. In this study, 23 refrigerants were considered at various composition. The present work considered the practical vapour compression refrigeration cycle for the performance assessment of various R22 alternatives. Essential studies such as toxicity, flammability, and total equivalent warming index of various novel refrigerants were also conducted in this study. Results obtained from practical vapour compression refrigeration cycle revealed that the energy efficiency ratio of refrigerants such as R1270 (2.860) and RB03 (R290/R152a of 60/40 in mass %) (2.854) was closer to the energy efficiency ratio of R22 (2.940). Volumetric refrigeration capacity (VRC) of R1270 (3293 kJ/m3) was similar to that of R22 (3297 kJ/m3) whereas VRC of RB03 (2908 kJ/m3) was almost similar to that of R407C (2925 kJ/m3) which was an alternative to R22. Compressor discharge temperature of RB03 was 15.78 ? lower when compared to R22. Flammability study revealed that all the new refrigerant blends (RB01 to RB04) were classified into weakly flammable (A2) and flammable (A3) category refrigerants whereas toxicity study revealed that all the investigated refrigerants were classified into non-toxic group (A). Refrigerant blend RB03 was less flammable compared to R1270. Total equivalent warming index analysis revealed that the environmental impact of R422A was 27.88% higher than R22 whereas RB03 has 4.97% lower environmental impact compared to R22. Overall, performance of refrigerant blend RB03 was better compared to 23 investigated refrigerants and it was very nearer to the performance of R22 and hence, it could be considered as an ecofriendly alternative to replace high global warming potential refrigerant R22 used in air conditioners. © IMechE 2020.