    Noniterative Method for Combined Acoustic-Electrical Partial Discharge Source Localization
    (Institute of Electrical and Electronics Engineers Inc., 2018) Antony, D.; Punekar, G.S.
    The combined acoustic-electrical system is used in the factory or plant environment for the partial discharge (PD) source localization in power transformers. A noniterative method for this combined acoustic-electrical PD-locator-system is devised and presented in this paper for the first time. It employs three acoustic emission (AE) sensors. The proposed method is compared with the existing noniterative method used in the all-acoustic system, which employs four AE sensors. The comparative study shows that the proposed method can locate the PD source irrespective of its position within the tank, whereas the prevailing noniterative method for the all-acoustic system fails to locate the PD source at certain positions within the tank. The effect of the sensor positioning on the performance of the method is studied, and some guidelines for the sensor placement on the transformers tank wall in a factory or plant environment are suggested. The proposed method is also applied to the data taken from the published literature. The localization results are compared with those of an existing iterative method (Newton's method) to prove its superiority in terms of computational time. © 1986-2012 IEEE.
  • Item
    Effects of transformer-oil temperature on amplitude and peak frequency of partial discharge acoustic signals
    (Institute of Electrical and Electronics Engineers Inc., 2018) Shanker, T.B.; Nagamani, H.N.; Antony, D.; Punekar, G.S.
    The behavior of partial discharge (PD) acoustic emission (AE) signals in the transformer oil for a temperature range of 30-75 °C is studied via laboratory experiments. The AE signals are analyzed using the fast Fourier transform (FFT) to obtain the peak frequency and the AE amplitude. A peculiar behavior of reduction in the peak frequency and the AE amplitude observed above 65 °C is reported. An attempt is made to explain the reduction in the AE amplitude after a certain temperature by correlating it with the properties of the transformer oil such as the viscosity and the breakdown voltage. This AE signal analysis is perhaps an important advancement in the PD diagnosis and the PD spectrum analysis at different temperatures in the transformer oil. © 1986-2012 IEEE.